Load Failure Monitoring - Siemens Sinamics G120P Operating Instructions Manual

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Functions
7.7 Application-specific functions
Table 7- 32
Parameter
Speed-dependent torque monitoring
p2181
p2182
p2183
p2184
p2185
p2186
p2187
p2188
p2189
p2190
p2192
p2193
For more information, see the List Manual (the parameter list and function diagram 8013).
7.7.9.3

Load failure monitoring

Using this function, the inverter monitors the load using an external signal. It can be fed in
from an encoder or a digital input, for example.
The inverter evaluates whether a load signal is available. If the load signal fails for a time
longer than that set in p2192, then the inverter outputs fault F07936.
Examples of how the function can be used:
● Drive belt monitoring for fans and conveyor belts
● Blocking protection for pumps and conveyor belts
Connect the load signal using p3223, for example p3232 = 722.4. In the factory setting, the
load failure monitoring function is not active.
Set the delay time for the fault message in p2192.
396
Parameters
Description
Load monitoring, response
Setting the response when evaluating the load monitoring.
0: Load monitoring disabled
>0: Load monitoring enabled
Load monitoring, speed threshold 1
Load monitoring, speed threshold 2
Load monitoring, speed threshold 3
Load monitoring, torque threshold 1, upper
Load monitoring, torque threshold 1, lower
Load monitoring, torque threshold 2, upper
Load monitoring, torque threshold 2, lower
Load monitoring, torque threshold 3, upper
Load monitoring torque threshold 3, lower
Load monitoring, delay time
Load monitoring configuration
0: Monitoring switched off
1: Monitoring torque and load drop
2: Monitoring speed and load drop
3: Load failure monitoring
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A