Fault Messages From Motor Sensors; F024 Fault Message From Free Function Block Fb3 (Active In All Operating States); F025 Brush Length Too Short (Active In Operating States Of ≤ 03); F028 Motor Overtemperature (Active In Operating States Of ≤ O6) - Siemens 6RA70 Series Instructions Manual

Microprocessor-based converters from 15a to 1680a for variable speed dc drives
Hide thumbs Also See for 6RA70 Series:
  • Faq (4 pages)
Table of Contents

Advertisement

Fault
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
F021
External fault 1
(active in all operating states)
Bit 15 in control word 1 was in the log. "0" state for longer than the time set in P360 index 001
F022
External fault 2
(active in all operating states)
Bit 26 in control word 2 was in the log. "0" state for longer than the time set in P360 index 002
F023
Fault message from free function block FB2
(active in all operating states)
Fault value:
1
the binector wired via parameter U100 Index.001 is in the state log."1"
2
the binector wired via parameter U100 Index.002 is in the state log."1"
3
the binector wired via parameter U100 Index.003 is in the state log."1"
4
the binector wired via parameter U100 Index.004 is in the state log."1"
F024
Fault message from free function block FB3
(active in all operating states)
Fault value:
1
the binector wired via parameter U101 Index.001 is in the state log."1"
2
the binector wired via parameter U101 Index.002 is in the state log."1"
3
the binector wired via parameter U101 Index.003 is in the state log."1"
4
the binector wired via parameter U101 Index.004 is in the state log."1"
9.1.2.4

Fault messages from motor sensors

F025
Brush length too short
(active in operating states of ≤ o3)
When parameter P495=2 (binary sensing of brush length), fault message at log."0" signal (longer than 10s) at terminal 211
Possible fault causes
♦ Encoder for brush length has responded
♦ Open circuit in encoder cable
F026
Bearings in bad condition
(active in operating states of ≤ o6)
When parameter P496=2 (bearing condition sensing) fault message at log. "1" signal (longer than 2 s) at terminal 212
Possible fault causes
♦ Encoder for bearing condition has responded
F027
Air-flow monitoring of motor fan
(active in operating states of < o6)
When parameter P497=2 (air-flow monitoring), fault message at log "0" signal (longer than 40s) at terminal 213
Possible fault causes
♦ Encoder for fan monitoring has responded
♦ Open circuit in encoder cable
F028
Motor overtemperature
(active in operating states of ≤ o6)
When parameter P498=2 (thermostat connected), fault message at log. "0" signal (longer than 10s) at terminal 214
Possible fault causes
♦ Thermostat for monitoring motor temperature has responded
♦ Open circuit in encoder cable
9-8
Description
Further information (r047.002 to r047.016)
SIMOREG DC Master Base Drive Panel Operating Instructions
Siemens Energy & Automation