PNU
Description
r653
Display of status word 2
Mode of representation on operator panel (PMU):
(G183)
Segments 0 to 15 correspond to bits 16 to 31 of the status word
Segment ON:
Segment OFF:
The following parameters are used to select the binectors (some of which are gated with one another or with other signals) to be applied to
the individual bits of the control word.
The settings of all these parameters are as follows:
0 = binector B0000
1 = binector B0001
etc.
The functions and logic operations are also shown on Sheets G180 and G181 in Section 8 of Operating Instructions 6RX1700-0AD**.

Control word 1

P654
Source for control word 1, bit0
*
(0=OFF1, 1=ON; ANDed with terminal 37)
BDS
(G130)
P655
1st source for control word 1, bit1
*
(0=OFF2; ANDed with 2
BDS
(G180)
P656
2nd source for control word 1, bit1
*
(0=OFF2; ANDed with 1
BDS
(G180)
P657
3rd source for control word 1, bit1
*
(0=OFF2; ANDed with 1
BDS
(G180)
P658
1st source for control word 1, bit2
*
(0=OFF3=Fast stop; ANDed with 2
BDS
(G180)
P659
2nd source for control word 1, bit2
*
(0=OFF3=Fast stop; ANDed with 1
BDS
(G180)
P660
3rd source for control word 1, bit2
*
(0=OFF3=Fast stop; ANDed with 1
BDS
(G180)
P661
Source for control word 1, bit3
*
(0=pulse disable, 1=enable; ANDed with terminal 38)
BDS
(G180)
P662
Source for control word 1, bit4
*
(0=set ramp-function generator to zero, 1=enable ramp-function generator)
BDS
(G180)
P663
Source for control word 1, bit5
*
(0=ramp-function generator stop, 1=ramp-function generator start)
BDS
(G180)
P664
Source for control word 1, bit6
*
(0=enable setpoint, 1=disable setpoint)
BDS
(G180)
P665
1st source for control word 1, bit7
*
(0 → 1 transition=acknowledge; ORed with 2
BDS
(G180)
10-68
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Corresponding bit is in log. "1" state
Corresponding bit is in log. "0" state
nd
rd
and 3
sources for bit1)
st
rd
and 3
sources for bit1)
st
nd
and 2
sources for bit1)
nd
rd
and 3
sources for bit2)
st
rd
and 3
sources for bit2)
st
nd
and 2
sources for bit2)
nd
rd
and 3
Value range
[Unit]
Steps
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
All binector numbers
1
sources for bit7)
SIMOREG DC Master Base Drive Panel Operating Instructions
No. indices
See
Factory
Change
setting
(Access /
Type
Status)
Ind: None
P052 = 3
Type: V2
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=1
P051 = 40
Type: L2
Offline
Ind: 2
P052 = 3
FS=0
P051 = 40
Type: L2
Offline