7SR210 & 7SR220 Applications Guide
Figure 2.5-2 Blocking Scheme Using Instantaneous Overcurrent Elements
Typically a time delay as low as 50 ms on the incomer 50-1 element will ensure that the incomer is not tripped for
outgoing circuit faults. However, to include for both equipment tolerances and a safety margin a minimum time
delay of 100 ms is recommended.
This type of scheme is very cost effective and provides a compromise between back-up overcurrent busbar
protection and dedicated schemes of busbar protection.
Instantaneous elements are also commonly applied to autoreclose schemes to grade with downstream circuit
reclosers and maximise the probability of a successful auto-reclose sequence – see section 4.
© 2013 Siemens Protection Devices Limited
Page 17 of 48