Siemens Argus 7SR21 Technical Manual page 151

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

Description
E3 Pickup Delay
Time before equation output operates, after equation satisfied
E3 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
E3 Counter Target
Select number of times equation must be satisfied before equation
output operates
E3 Counter Reset Mode
Select type of counter reset mode
E3 Counter Reset Time
Select counter reset time
E4 Equation
Enable or Disable logic equation E4
E4
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed
(requires E1 to drive L11 in output matrix)E1 =
F3^L11
E4 Pickup Delay
Time before equation output operates, after equation satisfied
E4 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
E4 Counter Target
Select number of times equation must be satisfied before equation
output operates
E4 Counter Reset Mode
Select type of counter reset mode
E4 Counter Reset Time
Select counter reset time
E5 Equation
Enable or Disable logic equation E5
E5
Specify logic equations of the form En =
<Operand><Operator><Operand>using the
following:0123456789=Digit() = Parenthesis! = NOT operation. =
AND operation^ = EXCLUSIVE OR operationE(followed by a digit) =
Equation numberF (Followed by a digit) = Function Key
numberI(Followed by a digit) = Binary Input numberL(Followed by a
digit) = LED numberO(Followed by a digit) = output relay
numberV(Followed by a digit) =Virtual Input/Output
number.ExamplesMake a function key LED toggle when function key
is pressed
(requires E1 to drive L11 in output matrix)E1 =
F3^L11
E5 Pickup Delay
Time before equation output operates, after equation satisfied
E5 Dropoff Delay
Time before equation output resets, after equation nolonger satisfied
E5 Counter Target
Select number of times equation must be satisfied before equation
output operates
Unrestricted ©2018 Siemens Protection Devices Limited
Range
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
Off, Multi-shot, Single-shot
0, 0.01 ... 14300, 14400
Disabled, Enabled
(20 Character String)
0, 0.01 ... 14300, 14400
0, 0.01 ... 14300, 14400
1, 2 ... 998, 999
7SR210 Settings Guide
Default
0 s
0 s
1
Off
0 s
Disabled
0 s
0 s
1
Off
0 s
Disabled
0 s
0 s
1
Page 27 of 61