Parameter Sets - Siemens FDA241 Technical Manual

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Planning
4
Operating modes
4.2.1
40
Building Technologies
Fire Safety

Parameter Sets

The following information applies to the 'Automatic: switches between blue and
blue-red based on ratio' mode.
FDA241
Set
No.
Inspect
0
0.07
1
0.03
2
0.03
3
0.04
4
0.05
5
0.07
6
0.08
7
0.18
8
0.30
9
0.40
10
0.80
FDA221
Set no.
Prealarm
0
0.50
6
0.14
7
0.28
8
0.50
9
0.70
10
1.40
Sensitivity [%/m]
Prealarm
Fire 1
0.10
0.15
0.04
0.05
0.045
0.06
0.055
0.07
0.075
0.10
0.10
0.15
0.14
0.20
0.28
0.40
0.50
0.70
0.70
1.00
1.40
2.00
Sensitivity [%/m]
Fire 1
0.70
0.20
0.40
0.70
1.00
2.00
Comment
Fire 2
20
default
2
2.5
3
4
5
6
8
10
15
20
Comment
Fire 2
20
default
6
8
10
15
20
A6V10334410_h_en_--