Siemens FDA241 Technical Manual page 25

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Display
Designation
Operating indication
Blowing-out indicator
Indication of faults
Airflow indicator
a) LED yellow
b) LED green
c) LED yellow
Building Technologies
Fire Safety
Function
The green LED lights up permanently:
When the power supply is connected
The yellow LED lights up permanently:
1
When the blowing-out process is activated
The yellow LED flashes:
Once the blowing-out process has been activated until the normal operating status
is achieved (lasts up to 2 minutes)
The yellow LED flashes:
When there is a technical fault
When the housing cover is opened
The current airflow is indicated by an LED in the airflow indicator (bar graph indicator).
If a yellow LED lights up, the airflow has increased.
As the deviation increases, the light moves upwards.
If the topmost LED flashes, the airflow has exceeded the upper limit and the alarm delay
time has expired.
Example: There may be a leak in the pipe system.
One of the green LEDs lights up.
The airflow is normal.
If a yellow LED lights up, the airflow is too low.
As the deviation increases, the indicator moves downwards.
If the bottommost LED flashes, the airflow has fallen below the lower limit and the alarm
delay time has expired.
Example: Some of the aspirating holes in the pipe system may be blocked.
Structure and function
Setup
A6V10334410_h_en_--
2015-09-29
3
25