Siemens Sinamics S120 Function Manual page 41

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Figure 1-8
Commissioning
The rated line voltage (p0210) must be parameterized during commissioning.
For the 20 kW and 40 kW Basic Line Modules booksize, the temperature switch of the
external braking resistor must be connected to X21 on the Basic Line Module.
If a braking resistor has not been connected for 20 kW and 40 kW Basic Line Modules
booksize, the braking chopper must be deactivated via p3680 = 1.
An optional braking chopper can be externally mounted on the Basic Line Module chassis. A
braking resistor must then be connected to the braking chopper.
Drive functions
Function Manual, (FH1), 01/2012, 6SL3097-4AB00-0BP2
Schematic structure of Basic Infeed chassis
Infeed
1.3 Basic Infeed
39

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents