Dr 45 Protocol Request; Overview; Protocol Id To Be Read - Siemens SIWAREX WP231 Manual

Hide thumbs Also See for SIWAREX WP231:
Table of Contents

Advertisement

8.23

DR 45 protocol request

8.23.1

Overview

Scale logs can be saved in the internal memory of the SIWAREX. If necessary, a log can be
read out calibration-proofed using the SIWATOOL V7 program or the SecureDisplay and its
contents checked.
Using data records DR 45/DR 46, you can read all logs into the SIMATIC S7 (not calibration-
proofed, only as operating information). The users enters the desired protocol ID in DR 45
and subsequently sends DR 45 to the SIWAREX. The protocol is then made available in DR
46 for reading out.
Table 8- 24
Assignment of data record 45
Variable
Note
Data record number
Contains no. of data record
Length
Data record length information
Application
Information about which applica-
tion the DR belongs to
Version identifier
Information about current data
record version
Reserve
Reserve
Reserve
Reserve
Reserve
Reserve
Protocol ID to be
ID of requested protocol entry as
read, decimal
decimal value
8.23.2

Protocol ID to be read

The protocol ID of the protocol to be displayed in data record 46 is entered at this point.
The report ID to be read is also used for reading of the report for legal trade use by means of
the SecureDisplay.
SIWAREX WP231
Manual, 07/2014, A5E31238908A-02
Type
Len
Rw
gth
(byt
es)
USHORT
2
r
USHORT
2
r
USHORT
2
r
USHORT
2
r
UBYTE[2]
2
rw
CHAR[12]
12
rw
USHORT
2
rw
LONG
4
rw
Scale parameters and functions
8.23 DR 45 protocol request
Default
Min.
Max.
45
28
101
1
1
65635
12,12
" "
-
-
0
0
1
Modbus regis-
ters
6000
6001
6002
6003
6004
6005
6011
6012
125