Trace evaluation:
● SLS function with SLS level 2 is activated (see bits "SLS active", "active SLS level bit 0"
and "active SLS level bit 1")
● Drive is accelerated beyond the SLS limit (time axis from approx. -400 ms)
● Exceeding the limit is recognized (time axis 0 ms)
● Safety fault is initiated (time axis 0 ms; bit "internal event" is set to 0)
● Fault response STOP B is initiated (time axis 0 ms; see bit "STOP A or B active" and
"SS1 active")
● Drive is decelerated to a standstill (see curve of Drive_1.r9714[0])
● Standstill reached (time axis from approx. 250 ms)
● STOP A (as follow-up response to STOP B) is activated (see bit "STO active"); at this
point the speed falls below the shutdown speed SS1 (p9560) (drops below the shutdown
speed SS1 before SS1 timer (p9556) has expired).
Not e
Time differences through internal c alculations
Small time differences (of the order of two to three safety cycles (here up to 36 ms)) are
caused by internal calculations and do not present a problem.
SLS with encoder with s top response "STOP C"
N o .
N o te:
The acceptance test must be carried out separately for each configured control and each SLS speed limit used.
Control can be realized without selection via TM54F, onboard terminals (CU310-2) or via PROFIsafe.
1.
Initial state
Drive in the "Ready" state (p0010 = 0)
Safety Integrated Extended Functions enabled (p9601.2 = 1)
Safety functions enabled (p9501.0 = 1)
Safety configured with encoder (p9506 = 0 or p9506 = 2)
No Safety faults and alarms (r0945[0...7], r2122[0...7], r9747[0...7]) at the drive and
TM54F; see note "Non-critical alarms" at the beginning of Section "Acceptance tests."
2.
It may be necessary to take measures in the higher-level controller to be able to exceed the active speed limit.
Note that the internal limits (r9733[0], r9733[1] and r9733[2]) are removed by selecting "Start acceptance test".
3.
Configure and activate trace recording.
Trigger: Trigger on variable - bit pattern (r9722.7 = 0)
Record the following values: r9714[0], r9721, r9722
Select the time interval and pretrigger so you can recognize when the active SLS limit
has been exceeded and the subsequent drive responses
Safety Integrated
Function Manual, (FHS), 07/2016, 6SL3097-4AR00-0BP6
D e scri p ti o n
A.3 Acceptance tests (recommendations)
Appendix
Sta tu s
443