12.93
Note:
The pulse frequency can be specified only in the quantization given in the table above. Other
frequency inputs are rounded up or down to the next closest table value, e.g. 3150 Hz to
3200 Hz.
1101
The calculation dead time is the time which elapses between the start of a current control
clock cycle (input of current setpoint) and the activation of the control voltage setpoints on the
gating unit ASIC. The standard default value is automatically loaded during initial start-up when
machine data M1102 is input. In order to make the setpoints on all power sections "valid"
simultaneously (to achieve uniform dynamic response), the time required to calculate the most
complex axis (double axis) is entered.
Setting values (worstcase), execution times:
Note:
Limits of calculation dead time (violation leads to error message)
MD 1101 <
MD 1101 <
_______
*
A preselection with synchronous sampling period (TPWM) with respect to the controller cycles can be made
via the toggle button.
©
Siemens AG 1992 All Rights Reserved
SINUMERIK 840C (IA)
More user manuals on
f
in Hz
PBM
2666.6....
2782.6....
2909.0....
3047.6....
3200
3368.4....
3555.5....
3764.7....
4000
4266.6....
4571.4....
4923.0....
5333.3....
5818.1....
6400
7111.1....
8000
Calc. dead time current closed-loop
Default value
Lower input limit
50
MD 1000 x 31.25 µs (=current controller clock cycle)
1
T
––––––––––––
=
–––––
4 x MD 1100
ManualsBase.com
7 Drive Machine Data (SIMODRIVE Drive MD)
T
in µs
PBM
375.0*
359.375
343.75
328.125
312.5*
296.875
281.25
265.625
250.0*
234.375
218.75
203.125
187.5*
171.875
156.25
140.625
125*
Upper input limit
0
124
40 µs = single-axis module
50 µs = double-axis module
PBM
4
6FC5197- AA50
7.2.2 FDD MD (data description - SW 3)
Active on
Power On
Units
µs
7–49