GE D90 Plus Instruction Manual page 28

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

DEVICE OVERVIEW
Application to series-compensated lines
In-zone transformer compensation
Load encroachment
Fault locator
18
For additional information, refer to:
Distance elements
on page 183
Plus
The D90
distance elements
Plus
The D90
provides enhanced stability and security by employing an adaptive distance
reach control to cope with the overreaching and sub-synchronous oscillations when
applied to, or in the vicinity of, series compensated lines. For directional integrity the relay
uses memory voltage polarization and a multi-input comparator is used to deal with
current inversion issues in series compensated lines.
For additional information, refer to:
Series compensated line protection application guidelines
Series compensated lines
Phase distance elements in the D90
of three-phase wye or delta transformers, allowing application of the D90
protection on generators. VTs and CTs can be installed independently of each other on
either side of the power transformer. The relay automatically compensates for transformer
connections, to guarantee accurate reach for any type of fault.
For additional information, refer to:
Phase distance settings
Phase distance applied to power transformers
The reliable load encroachment feature offers excellent discrimination between keep
loading conditions and fault conditions especially for long lines under heavy loads by
supervising the distance elements or any overcurrent element. This prevents unwarranted
tripping under heavy line load conditions and enables optimum operation of the line while
meeting regulatory requirements for the loading.
The following diagram illustrates distance quadrilateral characteristics supervised by load
encroachment function.
Figure 9: Load encroachment characteristic example
For additional information, refer to:
Load encroachment settings
The integrated fault locator provides distance to fault in kilometers or miles.
on page 627
on page 648
Plus
can be used to detect faults through different types
on page 186
on page 642
on page 216
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION
on page 223
Plus
for backup

Advertisement

Table of Contents
loading

Table of Contents