S3 PROTECTION
6–70
OUTPUT RELAY 4 to 6 / OUTPUT RELAY 5 to 6
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Thermal Protection (Start
Protection and Thermal Overload Curve) operation. When the SWITCHING DEVICE is
selected as BREAKER, the assignable output relays will be Output Relay 4~6. When the
SWITCHING DEVICE is selected as CONTACTOR, the assignable output relays will be
Output Relay 5~6.
BLOCK 1 to 3
Range: Off, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Element 1 to 16
Default: Off
Three blocking inputs are provided for Thermal Protection. When any of the selected
blocking inputs turns ON, Thermal Protection will be blocked.
339 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS