F040
Automatic Function Selection
Program Utilities Display Parameters
This parameter setting is used to configure multiple parameters with the setting
of only one parameter. From the selection below multiple parameters may be
set as indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect
until this parameter is changed or the individual settings are changed.
Set this parameter to Disable to set these parameters individually.
Note:
After performing the desired selection the EOI display returns to
Disabled though the selected function has been carried out (i.e.,
without this, if selection 1 is performed, F004 and F207 would
hold the RR terminal setting regardless of attempts to change the
settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — RR or V/II (V/I) Switched via Terminal Board
4 — EOI Frequency/Terminal Board Command
5 — EOI = Frequency and Command
Related
Default
Parameters
Settings
Command
Terminal
Mode
Board
F003
Frequency
RR
Mode 1
F004
Preset
S3 Terminal
F117
Speed 3
Frequency
Terminal
Priority
Board
F200
V/I Setup
0.0%
F201
Frequency
V/I
Mode 2
F207
N/C = No Change — the setting remains as it was before setting parameter F040.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
User Settings
3-RR or V/I
0-Disable 1-RR 2-V/I
via TB
N/C
N/C
RR
N/C
RR
Freq. Ref.
N/C
Priority
N/C
Terminal Board
N/C
20.0%
N/C
RR
V/I
Direct Access Number — F040
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
4-EOI/Freq.
5-EOI Freq/
CMD/TB
CMD
Terminal
EOI
Board
EOI
N/C
N/C
EOI
F040
85