Command Control Selections

The following is a listing with descriptions of the
Command Mode (F003) selections (Program 
Fundamental  Standard Mode Selection 
Command Mode Selection).
Settings:
0 — Terminal Block
Allows for Command control input via the
Terminal Board.
1 — Not Used
Unused.
2 — EOI (Keypad)
Used for EOI command control.
3 — RS485
Used to transfer commands to the ASD via 4-wire RS485.
4 — Communication Option Board
Use this setting if using the optional Communication Board for command control.
Frequency Control
Selections
The following is a listing with descriptions of the
Frequency Mode (F004) selections (Program 
Fundamental  Standard Mode Selection 
Frequency Mode 1).
Settings:
1 — V/I
Used when a 0 to 10 VDC analog input or a 0 –
20 mADC current input is used as the speed control input. Only one input signal type may be
used at a time. Set
2 — RR
Used for a 0 to 10 VDC analog input signal.
3 — RX
Used for a -10 to +10 VDC analog input signal.
4 — Not Used
Unused.
5 — EOI (Keypad)
Used for EOI frequency control.
6 — RS485
Used to transfer speed commands to the ASD via 4-wire RS485.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net