Starting the UPS

Turn the main circuit breaker (MCCB) on the back of the UPS (see pages 52-53) to the "ON" position
(the breaker should normally remain in the "on" position).
Check that the AC INPUT LED on the front panel (see
front panel may light for a moment when the input breaker is turned "on". This is normal. The UPS will
now be supplying power in the bypass mode.
When running the UPS for the fi rst time or after the power failure backup
operation, charge the batteries for at least 24 hours (input breaker "on") before
operating the connecting load.
Using the UPS without charging the battery shortens the battery backup operation
time, which could result in the destruction of data in case of a power failure.
Press RUN key to begin UPS operation (see page 34 for startup screens).
If the input breaker is turned off while UPS is in the bypass state, the output
power stops. Any load devices will lose power.
Ensure that all sensitive loads have been previously shut down.
Stopping the UPS
To stop the UPS, press the STOP key approximately 1 second until the
"off". The UPS is now in the bypass mode.
To completely stop the UPS, turn the input breaker at the back of the UPS to the "OFF" position.
1600EP Series Instruction Manual
page
32 and 33) lights 'green'. All LED's on the
CAUTION
CAUTION
LED changes from green to
27