Bosch 830 ES Manual page 22

Temperature modulated with electronic ignition suitable for heating potable water and space heating (intended for variable flow applications)
Table of Contents

Advertisement

22 | Installation instructions
Adjusting minimum power fan speed (P2)
To select fan speed:
▶ Press ON/OFF button
into ON.
▶ Press and hold simultaneously buttons
seconds, until display reads P2.
Fig. 27
▶ Press
to enter P2 adjustment. The current setting will appear on
P
the display (factory default).
+
▶ Press
or
to choose the fan speed suitable with your
installation, see table 23 and table 24.
▶ Press and hold ( 5 sec.) "Program" button
flashes, then the selected value is memorized.
Proceed directly to chapter 7.4 to confirm CO
are within range.
Attention residents of the Commonwealth of Massachusetts:
In the Commonwealth of Massachusetts the following regulation went
into effect on 12/30/2005:
(a)For all side wall horizontally vented gas fueled equipment installed in
every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less
than seven (7) feet above finished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of
installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gas fitter shall observe that a hard wired carbon
monoxide detector with an alarm and battery back-up is installed on the
floor level where the gas equipment is to be installed. In addition, the
installing plumber or gas fitter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services of qualified
licensed professionals for the installation of hard wired carbon
monoxide detectors.
a.In the event that the side wall horizontally vented gas fueled equipment
is installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be installed on the next
adjacent floor level.
b. In the event that the requirements of this subdivision can not be met
at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided,
however, that during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be installed.
2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon
monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
6 720 644 936 (2013/01)
+
or
and
for 3
P
until the display
P
values
2
Adjusting maximum power fan speed (P1)
To select fan speed:
▶ Press ON/OFF button
into ON.
▶ Press and hold simultaneously buttons
seconds, until display reads P2.
Fig. 28
▶ Press the minus button
to display P1.
▶ Press "Program" button
P
setting will appear on the display.
+
▶ Press
or
to choose the fan speed suitable with your
installation, see table23 and table 24.
▶ Press and hold ( 5 sec.) "Program" button
flashes, then the selected value is memorized.
Proceed directly to chapter 7.4 to confirm CO
are within range.
3. SIGNAGE. A metal or plastic identification plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8)
feet above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fueled heating appliance or equipment. The sign
shall read, in print size no less than one half (1/2) inch in size, "GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon
monoxide detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1 through 4.(b)
EXEMPTIONS: The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required
To Be Vented" in the most current edition of NFPA 54 as adopted by the
Board; and
2. Product approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT VENTING
SYSTEM REQUIRED. When the manufacturer of Product Approved side
wall horizontally mounted gas equipment provides a venting system
design or venting system components with the equipment, the
instructions provided by the manufacturer for the installation of the
equipment and the venting shall include:
1. Detailed instructions for the installation of the venting system or the
venting system components: and
2. A complete parts list for the venting system design or venting system.
(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING
SYSTEM NOT PROVIDED. When the manufacturer of a product approved
side wall horizontally vented gas fueled equipment does not provide the
parts for the venting of flue gases, but identifies "special venting
systems," the following requirements shall be satisfied by the
manufacturer:
+
or
and
P
to enter P1 adjustment. The current
until the display
P
values
2
for 3
830 ES