Temperature modulated with electronic ignition suitable for heating potable water and space heating (intended for variable flow applications)
Table of Contents

Advertisement

CAUTION:
▶ The vent system must be installed by a qualified
installer in accordance with these instructions. If
improperly installed, a hazardous condition such as
explosion or carbon monoxide poisoning could result.
Bosch Water Heating will not be responsible for
improperly installed appliances.
NOTICE:
▶ In areas where outside temperatures routinely come
close to freezing, sealed combustion operation is
required. Concentric termination or separate
terminations for combustion and vent, must be
installed on the same wall or roof surface; however,
never facing the direction of prevailing winds. Failure
to do so may result in heat exchanger freezing and
bursting. This failure is not covered under the
manufacturer's warranty.
WARNING: Appliance malfunction!
▶ Protect the exhaust and inlet from leaves and debris
by installing a screen on the end of the termination.
¼ " mesh minimum opening recommended on screen.
4.3.1 Vent material
Establish vent clearances that comply with the vent manufacturer's
specifications. In all cases, follow local codes. See table 5:
Item
Diam.
Exhaust Vent 3 or 4 inches
Intake Vent
PVC
Table 5 Venting Specifications
Horizontal venting systems only:
An optional stainless concentric vent/air intake termination can be used
to provide only one penetration point through the exterior wall (see fig.
8, 9 & 10). The concentric vent/air intake kit can be ordered from your
local wholesaler. (Part# ESHCK). Note: Only tee terminals are approved
for use with the concentric vent/air intake kit (see Table 6). Vent piping
and tee terminal used with kit must be from the same vent pipe
manufacturer. The appliance can also be installed with separate air
intake and exhaust piping (see Fig.16).
Fig. 8 Concentric kit part # ESHCK
830 ES
Material
Sealed single wall stainless steel
(AL29-4C)
Sealed PVC or any other rigid pipe
Fig. 9 Concentric kit vent assembly
Fig. 10 Concentric kit installation
[LA] 12 inches
[LB] 3 inches stainless steel pipe
Installation instructions | 11
6 720 644 936 (2013/01)