16.0 Specifications

Table 11: D6600 Specifications
Dimensions
D6600
(H x W x D)
Weight
D6600
Aluminum, dark gray, semi-gloss enamel.
Cabinet Finish
Power Input
AC Nominal Operating Range
AC Maximum Operating Range
Current Required
D6600 with one line card installed
For each additional line card or terminal
card pair
For network communications card
Standby Power
Use a UPS with the D6600. The receiver includes an external battery connection and battery harness. Use 12 V
rechargeable sealed lead-acid batteries. A 4-hour minimum standby power supply (UPS or battery) is required for
UL Certification (refer to Section 8.1 Connecting External Batteries on page 14 for battery size).
Telephone
RJ11C modular jacks, with 26 AWG or larger wire diameter.
Connections
FCC Registration
ESVUSA-25328-AL-N
The D6600 Receiver is Federal Communications Commission (FCC) registered under Part No. 68 using the
RJ11C Interconnect that can be ordered from your local telephone company.
Notice:
Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy, and if not installed according to the instruction manual, might cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which
case the user must correct the interference at his or her own expense.
Ringer Equivalence
0.4 B
Display
Screen size: (H x W)
LED
Inputs and Outputs
Listings and
Approvals
Bosch Security Systems | 2/05 | 4998122704E
Rack mount
Standalone
8.7 kg (19 lb)
This equipment was tested and found to comply with the limits for a Class "A" digital device, pursuant to
0.7 in. x 6.0 in. (1.8 cm x 15.2 cm) dot matrix LCD (5 x 7 dots per character).
Shows two separate lines of 40-characters each.
LED display section indicates receiver status and power.
One RS-232 interface port COM3 (middle connector on the CPU terminator card) for connection to an
automation computer.
One RS-232 interface port COM4 (upper connector of CPU terminator card) for connection to an external
serial printer, a PC, a modem, or a network.
One parallel printer port for connection to a parallel printer
Two programmable inputs on the D6610 CPU I/O wire harness included)
Two programmable outputs on the D6610 CPU I/O wire harness included)
Optional: One RS-232 interface port (COM1) for the Network Communications expansion option.
UL Central Station Fire (864)
UL Central Station Burglary (1610)
UL Police Station Connect (365)
FCC Part 15 Radiated/Conducted Emissions
FCC Part 68 Telecom
ULC
Industry Canada
D6600 | Operation and Installation Guide | Contents
7.0 in. x 19.0 in. x 19.5 in.
(18 cm x 48.3 cm x 49.5 cm)
7.0 in. x 17.75 in. x 19.5 in.
(18 cm x 45.0 cm x 49.5 cm)
120 V or 230 V
100 VAC to 120 VAC, 220 VAC to 230 VAC, 50/60 Hz
2.5 A maximum
Required battery current
Required UPS AC standby current
Required additional battery current
Required additional UPS AC standby current
Required additional battery current
Required additional UPS AC standby current
Austel Approved
CE Approved
NIST AES Certification
800 mA
350 mA
210 mA
35 mA
10 mA
10 mA
-
CTR-21
-
EN60950 Safety
-
EN55022 Radiated/
Conducted Emissions
31

Hide quick links: