Power Supply Modules (D6600 Only); Printer Specifications; Installation; All Installations - Bosch Conettix D6600 Installation And Operation Manual

Communications receiver/gateway
Hide thumbs Also See for Conettix D6600:
Table of Contents

Advertisement

Conettix D6600/D6100i | Installation and Operation Guide | 5.0
Removing the CPU Card
1. Remove power to the receiver (refer to Section
7.7 Removing Power to the Receiver on
page 14).
2. Carefully grasp the plastic grip on the CPU card.
Slide it 2 in. to 3 in. (50 mm to 75 mm) out of the
enclosure.
3. Unplug the 50-pin ribbon cable connecting the
user interface card to the CPU card. Be careful
not to bend the board when disconnecting this
cable. Grasp the plastic plug connected to the
CPU board at the end of the cable and gently pull
it away from the circuit board.
4. Pull the CPU card straight out of the card guide.
Replacing the CPU Card
1. Remove power to the receiver (refer to Section
7.7 Removing Power to the Receiver on
page 14).
2. Remove the defective CPU card from the
enclosure.
3. Align the top and bottom of the CPU card with the
card guides. Slide the card into the enclosure,
leaving 2 to 3 in. (50 mm to 75 mm) out to
connect the ribbon cable.
4. Connect the ribbon cable to the CPU card. Orient
the cable so the red stripe is up and slide the card
the remaining distance into the enclosure.
5. Restore power to the receiver.
5.0 Power Supply Modules
(D6600 Only)
The AC/DC (D6630) and DC/DC
(D6631) Power Supply Modules are not
field serviceable.
Contact the Bosch Security Systems,
Inc. National Repair Center at (800)
289-0096 for repair or replacement.

6.0 Printer Specifications

Parallel printer connection: Use the DB25 port on the
back of the D6600/D6100i rear panel to connect to a
standard parallel text printer.
Models: Safecom SC9002 (Star 300) requires
82.6 mm. (3.25 in) wide paper.
12

Power Supply Modules (D6600 Only)

7.0 Installation

7.1

All Installations

Install the D6600/D6100i Communications
Receiver/Gateway according to the National Electrical
Code (NEC), NFPA 70, the National Fire Alarm Code,
NFPA 72, and the local Authority Having Jurisdiction
(AHJ).
7.2

UL Installations

UL Standard 827 requires that any
central station listed for NFPA 72,
Central Station Protective Signaling, UL
Central Station Burglary or Police
Station Connect Service must have a
redundant receiver on the premises to
use if the primary receiver malfunctions.
The D6640 is not intended for new
installations, but is suitable for existing
or retrofit sites.
A UPS is required for UL Fire Applications
when using the D6600.
For UL installations of the D6100i, the
GlobeTek, Inc. Modem DA-42-18L
transformer shall be used.
The D6100i must be used with an UL
Listed PSDN compatible automation
system.
A "COMM FAIL" message may indicate
a compromise attempt.
To meet requirement UL 1610, Section
63.1: The number of separate signals on
a single channel are limited to 1000.
Exception: There is no limit to the
number of signals if the central-station
equipment is completely duplicated by
standby equipment and a switchover
can be accomplished in not more than
90 seconds without loss of signals
during this period.
Network Communication - The model D6100i receiver
has been evaluated for communication over a Third
Party Data Networks for the following Services when
used with a compatible control unit:
1. Standard Line Security for Central Station Burglar
Alarm Systems per UL 1610 and UL 365.
Bosch Security Systems, Inc. | 9/08 | 4998122704-04