Automation Link Monitoring (Com3) Through Cpu Programmable Output Ports; Figure 5: D6100I Communications Receiver/Table 10: Terminator Card Configuration - Bosch Conettix D6600 Installation And Operation Manual

Communications receiver/gateway
Hide thumbs Also See for Conettix D6600:
Table of Contents

Advertisement

Conettix D6600/D6100i | Installation and Operation Guide | 9.0
.
Operating the input as an analog input
between 0.5 V and 5 V might cause
abnormal results. This input state is not
defined and might change expected
results
Reverse configuration is not for use in
UL Listed applications.
9.2
Automation Link Monitoring
(COM3) through CPU
Programmable Output Ports
The output connections on the I/O port have an open
collector transistor output that can activate an
external sounder or light if the automation system
fails.
Configure external devices using the
specifications listed in Table 10. Outputs
are not verified by UL.
Table 10: Terminator Card Configuration
Radionics D6615 CPU
Terminator Card
Solid state output provides
a current sink to common
(-)
Maximum load is 20 mA
Vsat @ 1 mA = 0.5 VDC
Vsat @ 10 mA = 3.0 VDC
Maximum voltage =
30 VDC
Bosch Security Systems, Inc. | 9/08| 4998122704-04
Bosch D6615 CPU
Terminator Card
Solid State output provides
a current sink to common
(-)
Maximum load is 75 mA
Vsat @ 10 mA = 0.5 VDC
Vsat @ 25 mA = 1.0 VDC
Vsat @ 50 mA = 2.5 VDC
Maximum voltage =
30 VDC
Input and Output Ports