Representation Of Analog Values In Voltage Measuring Ranges - Siemens 181 Workshop Manual

Analog input module ai 4xrtd/tc 2-/3-/4-wire hf (6es7134-6jd00-0ca1)
Table of Contents

Advertisement

Representation of analog values
B.2 Representation of analog values in voltage measuring ranges
B.2

Representation of analog values in voltage measuring ranges

The following tables list the decimal and hexadecimal values (codes) of the possible voltage
measuring ranges.
Table B- 4
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
Table B- 5
Values
Dec.
32767
32511
27649
27648
20736
1
0
-1
-20736
-27648
-27649
-32512
-32768
64
Voltage measuring range ±1 V
Hex.
7FFF
7EFF
6C01
6C00
5100
1
0
FFFF
AF00
9400
93FF
8100
8000
Voltage measuring range ±500 mV to ±50 mV
Voltage measuring range
Hex.
±250 mV
7FFF
> 294.0 mV
7EFF
294.0 mV
6C01
6C00
250 mV
5100
187.5 mV
1
9.04 µV
0
0 mV
FFFF
AF00
-187.5 mV
9400
-250 mV
93FF
8100
-294.0 mV
8000
<-294.0 mV
Analog input module AI 4xRTD/TC 2-/3-/4-wire HF (6ES7134-6JD00-0CA1)
Voltage measuring range
±1 V
> 1.176 V
1.176 V
1 V
0.75 V
36.17 µV
0 V
-0.75 V
-1 V
-1.176 V
<-1.176 V
±80 mV
±50 mV
> 94.1 mV
> 58.8 mV
94.1 mV
58.8 mV
80 mV
50 mV
60 mV
37.5 mA
2.89 µV
1.81 µV
0 mV
0 mV
-60 mV
-37.5 mV
-80 mV
-50 mV
-94.1 mV
-58.8 mV
<-94.1 mV
<-58.8 mV
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Range
Overflow
Overrange
Nominal range
Underrange
Underflow
Manual, 02/2014, A5E03573289-AD