3–66
"P" Group: Expansion Card Functions
Func.
Name
Code
P022
Feed-forward gain
setting
P023
Position loop gain
setting
P025
Temperature compensa-
tion thermistor enable
P026
Over-speed error
detection level setting
P027
Speed deviation error
detection level setting
P031
Accel/decel time input
selection
P032
Positioning command
input selection
P044
DeviceNet comm
watchdog timer
P045
Inverter action on
DeviceNet comm error
P046
DeviceNet polled I/O:
Output instance number
P047
DeviceNet polled I/O:
Input instance number
P048
Inverter action on
DeviceNet idle mode
P049
DeviceNet motor poles
setting for RPM
"P" Function
Description
Range is 0.00 top 99.99 /
100.0
Range is 0.00 to 99.99 /
100.0
Allows for motor-mounted
thermistor to calibrate
output to motor temperature
Two option codes:
00 Disable
01 Enable
Range is 0.0 to 150.0%
Range is 0.00 to 99.99 /
120Hz
Three options:
00 Inverter
01 Expansion card 1
02 Expansion card 2
Three options:
00 Inverter
01 Expansion card 1
02 Expansion card 2
Range is 0.00 99.99 seconds
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
Three settings:
20, 21, 100
Three settings:
70, 71, 101
Five options:
00 Trip
01 Decelerate and trip
02 Hold last speed
03 Free run stop
04 Decelerate and stop
Range is 00 to 38 (even
numbers only)
NOTE: Parameters P044 to P049 are available only in inverters with manufacturing code
x8K xxxxxx xxxxx or later. The manufacturing code is printed on the product specifications
labels, located on the front and side of the inverter housing.
Defaults
Run
Mode
Edit
–FE
–FU
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✔
0.00
0.00
0.00
✘ ✔
0.50
0.50
0.50
✘ ✔
00
00
00
✘ ✔
135.0 135.0 135.0
✘ ✔
7.50
7.50
7.50
✘ ✘
00
00
00
✘ ✔
00
00
00
✘ ✘
1.00
1.00
1.00
✘ ✘
01
01
01
✘ ✘
21
21
21
✘ ✘
71
71
71
✘ ✘
01
01
01
✘ ✘
0
0
0
SRW Display
Units
>P022 FEEDBACK
FFWG
000.00
>P023 FEEDBACK
G
000.50
>P025 FEEDBACK
R2-ADJ
OFF
%
>P026 FEEDBACK
0SPD
135.0%
>P027 FEEDBACK
NER
007.50Hz
>P031 ACC/DEC
SELECT
REM
>P032 P-SET
SELECT
REM
>P044 DEVICENET
TIMER
01.00s
>P045 DEVICENET
T-OUT
FTP
>P046 DEVICENET
O-AS-INS
021
>P047 DEVICENET
O-AS-INS
071
>P048 DEVICENET
IDLE
FTP
poles
>P049 DEVICENET
P
00P

Advertisement