Hitachi SJ300 Series Instruction Manual page 119

Hitachi instruction manual inverter sj300 series
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Option
Terminal
Code
Symbol
24
PIDC
PID Reset
26
CAS
Control gain setting
27
UP
Remote Control
UP Function (motor-
ized speed pot.)
28
DWN
Remote Control
DOWN Function
(motorized speed pot.)
29
UDC
Remote Control Data
Clearing
31
OPE
Operator Control
32
SF1
Multispeed bit 1
33
SF2
Multispeed bit 2
34
SF3
Multispeed bit 3
35
SF4
Multispeed bit 4
36
SF5
Multispeed bit 5
37
SF6
Multispeed bit 6
38
SF7
Multispeed bit 7
Input Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Description
Resets the PID loop controller. The main conse-
quence is that the integrator sum is forced to zero.
No effect on PID loop controller
Selects alternate parameters H070 to H072 for the
source of the internal speed loop gain
Selects parameters H050 to H052 (or H250 to H252
for 2nd motor) for the source of internal speed loop
gain
Accelerates (increases output frequency) motor from
current frequency
No change to output frequency
Decelerates (decreases output frequency) motor from
current frequency
No change to output frequency
Clears the UP/DWN frequency memory by forcing it
to equal the set frequency parameter F001. Setting
C101 must be set=00 to enable this function to work.
UP/DWN frequency memory is not changed
Forces the source of the output frequency setting
(A001) and the source of the RUN command (A002)
to be from the digital operator
Source of output frequency set by (A001) and source
of run command set by (A002) is used
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
Logical 1
Logical 0
3–51
SJ300 Inverter

Advertisement

Table of Contents
loading

Table of Contents