B–24
ModBus Data Listing
The table below lists the holding registers for the "F" Group Main Profile Parameters.
Func.
Code
F001
Output frequency
setting
F002
Acceleration (1) time
(high)
setting *1
F002
(low)
F202
Acceleration (1) time
(high)
setting, 2nd motor *1
F202
(low)
F003
Deceleration (1) time
(high)
setting *1
F003
(low)
F203
Deceleration (1) time
(high)
setting, 2nd motor *1
F203
(low)
F004
Keypad Run key routing R/W Two options; select codes:
Note 1:
Holding Registers, "F" Group Main Profile Parameters
Name
R/W
R/W Standard default target
frequency that determines
constant motor speed,
range is 0.0 / start frequency
to 400 Hz
R/W Standard default acceleration,
range is 0.01 to 3000 sec.
R/W
R/W Standard default acceleration,
2nd motor,
range is 0.01 to 3000 sec.
R/W
R/W Standard default deceleration,
range is
0.01 to 3000 sec.
R/W
R/W Standard default deceleration,
2nd motor,
range is 0.01 to 3000 sec.
R/W
00... Forward
01... Reverse
When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored.
Description
Reg.
0023h
0024h
0025h
0026h
0027h
0028h
0029h
002Ah
002Bh
002Ch
Network Data
Range
Res.
0 / (start
0.1 Hz
freq. x 10)
to 4000
1 to
0.01
300000
sec
1 to
0.01
300000
sec
1 to
0.01
300000
sec
1 to
0.01
300000
sec
0, 1
—