“C” Group: Intelligent Terminal Functions - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

"C" Group: Intelligent Terminal Functions
The six input terminals [1], [2], [3], [4], [5], and [6] can be configured for any of 19
different functions. The next two tables show how to configure the six terminals. The
inputs are logical, in that they are either OFF or ON. We define these states as OFF=0,
and ON=1.
The inverter comes with default options for the six terminals. These default settings are
initially unique, each one having its own setting. Note that European and US versions
have different default settings. You can use any option on any terminal, and even use the
same option twice to create a logical OR (though usually not required).
NOTE: Terminal [6] has the ability to be a logical input, and to be an analog input for a
thermistor device when the PTC function (option code 19) is assigned to that terminal.
Input Terminal Configuration
Functions and Options –The function codes in the following table let you assign one of
nineteen options to any of the six logic inputs for the SJ200 inverters. The functions
C001through C006 configure the terminals [1] through [6] respectively. The "value" of
these particular parameters is not a scalar value, but it is a discrete number that selects
one option from many available options.
For example, if you set function C001=00, you have assigned option 00 (Forward Run)
to terminal [1]. The option codes and the specifics of how each one works are in
Chapter 4.
Func.
Name /
Code
SRW Display
C001 Terminal [1] function
IN-TM 1
C002 Terminal [2] function
IN-TM 2
C003 Terminal [3] function
IN-TM 3
C004 Terminal [4] function
IN-TM 4
C005 Terminal [5] function
IN-TM 5
C006 Terminal [6] function
IN-TM 6
"C" Function
Description
Select terminal [1] function,
24 options (see next section)
FW
Select terminal [2] function,
24 options (see next section)
RV
Select terminal [3] function,
24 options (see next section)
AT
Select terminal [4] function,
24 options (see next section)
USP
Select terminal [5] function,
24 options (see next section)
2CH
Select terminal [6] function,
24 options (see next section)
RS
SJ200 Inverter
Defaults
Run
Mode
–FEF
–FU
Edit
(EU)
(USA)
00
00
[FW]
[FW]
01
01
[RV]
[RV]
02
16
[CF1]
[AT]
03
13
[CF2]
[USP]
18
09
[RS]
[2CH]
09
18
[2CH]
[RS]
3–41
Units

Advertisement

Table of Contents
loading

Table of Contents