Conettix D6600/D6100i | Installation and Operation Guide | 10.0 D6600/D6100i Operation
.
3
D6600
D6100i
M/E
ENTER
4
D660 0
D610 0i
6
6
5
The LCD changes all
segments to black for 2 sec so
that you can check for non-
functioning LCD segments.
All D6641 Line Cards will turn
the line LEDs on red for 2 sec
D6600
D6100i
and then green for 2 sec.
M/E
ENTER
The Power and System
trouble LEDs will turn on for
2 sec, then off.
After the test is complete, the
system restores the LEDs to
their previous state.
Bosch Security Systems, Inc. | 6/09 | 4998122704-06
10.5

Busy Seconds (Line Busy) Reports

The D6600/D6100i monitors and reports when a call
group of receiver lines cannot receive signals. The
receiver cannot process signals if its incoming
telephone lines are in trouble, if other communicators
have the line tied up, or if the line card is inoperative.
The receiver interprets these conditions as busy time.
The amount of busy time accumulated during a 10
min period is the basis for a Busy Seconds Reports.
The 10 min busy period begins when all lines in a call
group become busy, or when a non-programmed
single line for a call group becomes busy. The
D6600/D6100i totals the accumulated busy time and
prints the Busy Seconds Report after the 10 min
period ends. After at least 60 sec (10%) of busy time,
the receiver generates a report. The D6600/D6100i
reports up to 100% busy time.
Program the Busy Seconds Reports option to No if
Busy Seconds Reports are not wanted for all lines.
Setting the Line Sniff option to 2 disables reports for
individual lines.
Enable Seconds Reports for UL Listed
central stations.
UL inspectors might investigate the amount of time
the digital receiver lines cannot receive signals.
Ensure that lines are available to process emergency
signals on a timely basis. Excessive Line Busy
Reports can indicate it is necessary to install
additional lines in rotary with your primary receiver
lines.
Assign each line to a call group. For the group to start
accumulating busy time, all lines in the call group
must be online, in trouble, or without an operating line
card.
Although it is not mandatory, not
assigning a line to a call group, or when
there is only one line in the group, 1 min
of busy time during a 10 min period
results in a Busy Seconds Report.
If you do not assign a line to a call group, displays
and printer reports identify the line number instead of
the Group number. A Line Busy Report shows and
prints: