Buzzer Operation; Reporting Devices: Primary And Secondary; Normal Operation Mode - Bosch Conettix D6600 Installation And Operation Manual

Communications receiver/gateway
Hide thumbs Also See for Conettix D6600:
Table of Contents

Advertisement

Conettix D6600/D6100i | Installation and Operation Guide | 10.0 D6600/D6100i Operation

10.1.6 Buzzer Operation

In the Manual Mode, an Operator Alert Buzzer sounds
when a message is received until you press the
[ACKNOWLEDGE] key. The buzzer operation is
programmable and can be disabled when the receiver
is programmed for the Automatic Mode.

10.1.7 Reporting Devices: Primary and Secondary

A reporting device is any device that can print or
display messages from the D6600/D6100. This includes
the central station automation computer or an external
printer. You can enable the external printer and
designate it as the primary or secondary device. The
automation computer is always a primary device unless
disabled. Primary reporting devices receive all reports
generated by the D6600/D6100i. Secondary reporting
devices only receive input from the D6600/D6100i
when all primary devices fail.
UL 1981 allows the receiver to suppress
printing during normal automation system
operation if the printer starts printing upon
automation system failure.
If the receiver is in the Automatic Mode and all of the
primary reporting devices (such as printers and
computers) fail, the receiver re-routes the messages to
the secondary reporting device(s). If you program the
receiver for no secondary reporting devices or if all
secondary reporting devices fail, the D6600/D6100i
automatically switches to Manual Mode. When the
receiver restores automation to normal operation, the
D6600/D6100i returns to the Automatic Mode if the
user manually acknowledges the last buffered signal.
18
10.2

Normal Operation Mode

In Normal Operation Mode, the D6600/D6100i sends
messages immediately or in blocks to reporting devices
(such as printers and computers) as soon as the devices
are ready to receive the information. Signals do not
remain visible in the display. If all reporting devices
fail, the D6600/D6100i reverts to Manual Mode until a
device returns to service. Normally, the D6600/D6100i
sounds the Operator Alert Buzzer for new events
received when the automation link fails.
Typical Alarm Receiving Sequence
1. An alarm occurs on Zone 3 at subscriber location
456. The user programs Account 456 to report to
Line 01 and does not assign Line 01 to report to a
call group.
2. The OL LED glows green when the receiver
answers the call and receives data.
3. The primary reporting device(s) (such as external
printer or automation computer) activates.
If the external printer is a primary reporting device
and Line 01 is not assigned to Group Reporting, it
prints:
If Line 01 is assigned to Group 1 Reporting, the
receiver's external printer prints:
4. Line 01 hangs up