D400 SYSTEM REDUNDANCY

Minimal required connection

D400 system redundancy

Failover sequence

66
Figure 41: Front serial port
The minimal cable connection required to establish successful communication between
your PC and the D400 is as follows:
PC Pin #
9-Pin Female
2
3
5
A redundant D400 setup allows a secondary D400 to automatically take over operations
from a paired D400 unit that has failed.
D400 equipment redundancy requires two D400 units and one or two RS232 switch panels.
The RS232 switch panel is mandatory for Warm Standby redundancy.
If the Hot Standby redundancy feature is available, the RS232 switch panel is optional.
A pair of LEDs marked CCU A and CCU B indicate which of the D400 units is currently active.
If the hardware or software of the active unit fails, it is automatically switched offline and
serial connections to the field are transferred to the standby unit. A toggle switch on the
RS232 switch panel can be used to switch the D400 devices between active and standby
modes.
If the active D400 unit fails, the following actions occur:
1.
The standby D400 unit detects the failure through the lack of a heartbeat signal on the
ping cable or through a status change on the watchdog cable.
2.
The standby D400 unit attempts to pull the RS232 switch panel to assume the active
state.
3.
The RS232 switch panel transfers all serial field connections to the standby D400,
which then becomes the active D400.
CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS
D400 Pin #
9-Pin Female (w/o Converter)
3
2
5
GENERAL
D400 SUBSTATION GATEWAY USER'S MANUAL
Signal Acronym
TXD
RXD
GND