2 | DS9400M AddressiFire Fire Alarm Control Panel
Smoke detector alarm verification
Should an alarm occur, the DS9400M may be programmed
to perform an automatic reset on the smoke detectors. If a
second alarm on any smoke input point occurs within the
verification window, an immediate fire alarm results. This
reduces potential false alarms, while still providing fast
response to an alarm.
Flexible digital communication
The communicator will work with most alarm receivers that
are in use today. It supports SIA (110 or 300 Baud), Contact
ID, BFSK, and 4/2 Tone burst digital communicator formats.
EE Memory
The panel uses EEPROM technology, thereby allowing it to
retain all program memory through a total power failure.
None of the system programming or user codes will be lost.
Three telephone numbers
The systems supports two 20-digit telephone numbers with
a three- or four-digit account code for each. Each phone
line's dialing type can be configured for either pulse or tone
dialing. The communication format for each phone number
can also be set. The third phone number is reserved for
remote programming.
Event history buffer
A 500 event history buffer, which can be read at the built-in
or DS9447 keypads, keeps track of events by time and date.
Commercial Fire
Type Service: Auxiliary, Local, Central Station, and Remote
Station.
Type Initiating: Automatic, Manual, Sprinkler Supervisory
and Waterflow.
Installation/Configuration Notes
Keypads:
Up to four keypads may be used in the system with a
maximum wire length of 300 m (1000 ft.) each.
Note
No more than two keypads per 300 m (1000 ft.)
run.
Wiring:
The maximum wire length total in the system is 1220 m
(4000 ft.) using 0.8 mm (#22 AWG) or 1.0 mm (#18 AWG)
4-conductor cable.
Americas:
Europe, Middle East, Africa:
Bosch Security Systems, Inc.
Bosch Security Systems B.V.
130 Perinton Parkway
P.O. Box 80002
Fairport, New York, 14450, USA
5600 JB Eindhoven, The Netherlands
Phone: +1 800 289 0096
Phone: + 31 40 2577 284
Fax: +1 585 223 9180
Fax: +31 40 2577 330
security.sales@us.bosch.com
emea.securitysystems@bosch.com
www.boschsecurity.us
www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1113381259 | Cur: en-US, V2, 4 Jul 2010

Technical Specifications

Enclosure Design
Dimensions (HxWxD):
Material:
Environmental Considerations
Temperature (Operating):
Inputs
Supervisory EOL Resistor:
Keypads:
Outputs
Relays (On-Board):
NACs (on-board):
Power Requirements
Power (Auxiliary):
Power (Initiating Circuit):
Power (Input):
Power (NAC):
Power (Open Bus):
Standby Batteries:
Standby Current (Detector):

Ordering Information

DS9400M AddressiFire Fire Alarm Control
Panel
Accessories
DS9432 Addressable 8-Point Input Module
DS9434 Four-Point Expander
DS9446 Eight‑zone LED Expander
DS9488 Octal Relay Module
Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
apr.securitysystems@bosch.com
www.boschsecurity.com
53 cm. x 38.1 cm. x 11.0 cm (20.8 in. x
15.0 in. x 4.3 in)
The standard enclosure is manufactured
from 1.2 mm (18 guage) cold-rolled steel.
A keyed lock is included, and the LEDs and
display are visible through the door.
0°C to +49°C (+32°F to +120°F)
2.21 kΩ
Maximum four keypads.
Two Form "C„ relays rated at 5 A, 28 VDC.
Programmable for a variety of system
events.
Two: NAC 1 and NAC 2. These are 24 V
outputs for notification devices, with up to
2.5 A capacity (but limited by overall 4.0 A
capacity) on each circuit. Wired for stand-
ard Class B operation.
20 VDC to 30 VDC unfiltered, 1 A
20.4 VDC to 28.2 VDC filtered, 1 A
120 VAC, 1.5 A
20 VDC to 30 VDC unfiltered, 4 A
12 V±5%, 500 mA
Two (optional) 12 V (in series),
7 Ah to 40 Ah
3 mA maximum total per point
DS9400M
DS9432
DS9434
DS9446
DS9488