Conettix C900V2 | Installation Guide | 7.0
.
Table 11: Connection Sequence – C900V2 and Generic Control Panel in Separate Enclosures
(UL Standard 864)
C900V2 Connection
Seq
1
RJ-45 PANEL connector
2
RJ-45 ETHERNET connector
3
– V terminal
4
V +
5
6
7
8
Install an EOL resistor for the
control panel across OUT2-L
and OUT1-R
9
OUT2-L to OUT1-L
10
OUT2-R to OUT1-R
11
OUT1-R
12
13
14
OUT2-L
15
16
17
18
NOTE: The sequence numbers appear in the diagram in Figure 13.
Bosch Security Systems, Inc. | 8/08 | F01U087780-01
Control Panel Connection
to
RJ-45 connector (telco dialer)
to
to
to
to
24-hour zone input common
to
24-hour zone input
Battery negative input
Battery positive input
AC input
AC input
UL Standard 864 for Fire System Installations
Other Connection
LAN or WAN
–12 to –24 VDC (common)
+12 to +24 VDC output
Power supply +BAT input to
battery 1 + terminal
Power supply –BAT input to
battery 2 – terminal
Battery 1 – terminal to battery 2 +
terminal (in series)
C900V2 enclosure closed-circuit
tamper switch
C900V2 enclosure closed-circuit
tamper switch to control panel
enclosure closed-circuit tamper
switch
to
Control panel enclosure closed-
circuit tamper switch
to
Battery negative terminal
to
Battery positive terminal
AC transformer
AC transformer