Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Fire brigade alerted, indicating that the "Fire brigade tx"
output is activated in EBL512 G3 because:
- the activated fire alarm is not an AA alarm
- the AA function has been ended, e.g. the acknowledge or
investigation time respectively has run out, etc.
Acknowledge, indicating that the AA alarm has been
acknowledged.
The unit has the following push buttons:
Alarms queued, used to scroll amongst the alarms.
Acknowledge, used to acknowledge an AA alarm and hereby
also silence the buzzer.
Reset, used to reset an AA alarm.
The unit shall run in S/W mode 1735 – 1587. Up to 1200 m
cable can be used.
description MEW00224.
1736 Alert Annunciation Unit (AAU). This unit is like 1735, except
it has a neutral front, where the designation texts, in any
language, are made separately and by production put into a
transparent "text slot" for the LED and push button respectively.
(This front also holds one extra LED & two extra push
buttons.).
The unit shall run in S/W mode 1736 – 1587. Up to 1200 m
cable can be used.
description MEW00224.

External Presentation Units

1728 External Presentation unit (EPU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly, when required. The
push buttons are disabled until they are supposed to be used.
The unit shall be wall mounted. Two compression glands are
attached. The front's designation texts are in Swedish. This
unit is intended for pre-warning, co-incidence
smoke / heat) alarm presentation. If there are two or more
alarms in the system, you can scroll amongst them but the fire
alarms cannot be reset via this unit.
All or selected alarms will be presented in a display (alpha-
numeric LCD, 2x40 characters), with back-light. An alarm text
will also be presented together with each alarm, if programmed
in EBL512 G3. Furthermore, at least 617 texts can for selected
fire alarms be stored in the unit and will in such a case be
shown, instead of the texts sent out from EBL512 G3 for these
alarms. These text messages will be downloaded to the unit via
46
Two zone / address dependence.
For more information, see Technical
For more information, see Technical
57
46
, fire (and heavy

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3

Table of Contents