Alert Annunciation Units - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
9.2.2
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
get access to the push buttons. They are disabled until they are
supposed to be used. The unit shall be wall mounted. Two
compression glands are attached. In all other respects it is like
1826, except that a printer cannot be mounted in 1828.
The unit shall run in S/W mode 1826/28 – 1587. Up to 1200 m
cable can be used.
description MEW00249.
1835 Printer. Can be mounted in the External Fire Brigade Panel
1826. It will print all the alarms, including the alarm texts.
Note that the printer current consumption is up to 200 mA when
printing.

Alert Annunciation Units

When the Alert Annunciation (AA) function shall be used in system
EBL512 G3, a unit is required for the related manoeuvres, i.e. to
acknowledge / reset the AA alarms. For a detailed description of the
Alert Annunciation function, see chapter "Alert Annunciation", page
102.
1735 Alert Annunciation Unit (AAU). A compact size enclosure
(HxWxD, 145 x 220 x 50 mm) made of grey high impact ABS.
Fitted with a supplementary "O" ring gasket, it will comply
with IP61, in respect of dust and moisture. The unit has no
door, i.e. the front is accessed directly but the push buttons are
disabled until they are supposed to be used. The unit shall be
wall mounted. Two compression glands are attached. The
front's designation texts are in Swedish.
All or selected fire alarms will be presented in a display
(alphanumeric LCD, 2x40 characters), with back-light.
alarm text will also be presented together with each alarm, if
programmed in EBL512 G3. Furthermore, at least 617 texts
can for selected fire alarms be stored in the unit and will in such
a case be shown, instead of the texts sent out from EBL512 G3
for these alarms. These text messages will be downloaded to
the unit via EBL512 G3.
indicate a not acknowledged AA alarm.
New software versions can be downloaded directly in the unit.
The unit is power supplied from EBL512 G3 or an external
power supply.
The unit has the following LEDs:
Fire and Alarms queued, indicating fire / AA alarm.
Operation, indicating that the unit is in operation, i.e. the AA
function is enabled in the system. A time channel can be used
to enable the AA function.
For more information, see Technical
A built-in buzzer will sound to
56
An

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ebl512 g3

Table of Contents