Panasonic EBL128 Planning Instructions page 38

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.1.1.4
6.1.1.5
L-35, N-15 or N-35 and for the heat detector set to one of three
algorithms for class A1 (static response temp. 54-65°C), A2 S
(54-70°C) or B S (69-85°C).
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
4301 Analog photo electric smoke detector.
reflection of infrared light) is used to detect smoke.
The detector has unleaded soldering.
To be plugged in an ASB base 3312. Built-in LEDs are lit to
indicate that the detector has generated fire alarm. Prepared for
mechanical lock (screw attached).
The technical address is set with an Address setting tool (AST)
3314.
The detector has an address label on which the
programmed technical address is to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: 4301 in this mode is in Win128 set to one of
the six algorithms H-15, H-35, L-15, L-35, N-15 or N-35.
2330 mode: Not used in EBL128.
2312 mode: Not used in EBL128.
Conventional Detector Bases (CDB)
2324 Base. A conventional detector is to be plugged in 2324. Built-
in LED that is lit to indicate that the detector plugged in the
base has generated fire alarm. Terminals for ext. LED 2217 /
2218.
Conventional Detectors
4318 Combination heat detector. Rate-of-rise and fixed temperature,
59°C, heat detector class A1 R. Static response temp. range 54-
65°C, ambient temp. min./typical/max. -10/+25/+50°C .
Has replaced 2318. To be plugged in a CDB 2324.
4350 Multi detector. A smoke detector and a heat detector within
one housing. Scattered light (i.e. reflection of infrared light) is
used to detect smoke and the heat sensing element is a
thermistor. In order to secure the fire detection and to prevent
false (nuisance) alarms, the AI function is used, i.e.
a: combined heat and smoke sensing
b: variable delay function
c: adaptive learning function
See also chapter "Cyber sensor functions", page 111.
The detector has unleaded soldering.
To be plugged in a CDB 2324.
4352 Photoelectric smoke detector. Scattered light (i.e. reflection of
infrared light) is used to detect smoke. An advanced alarm
EBL128 Planning Instructions V1.1.x
36
Scattered light (i.e.

Advertisement

Table of Contents