Limitations; C.i.e - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
23
23.1

Limitations

C.i.e.

Max. number of "items":
Item
Fire alarms (presented in the EBL128
display as ZONE and/or ZONE-
156
ADDRESS)
Faults
Trigger conditions (in all the control
expressions)
Interlocking Combinations
3361 units + 3364 units
3377 units + 3378 units
Total number of detectors and/or manual
call points
Max. number of AAF zones
Max. number of detectors per AAF zone
Max. number of I/O Matrix boards, incl.
all kinds of expansion boards
Max. number of outputs per c.i.e. incl.
all kinds of outputs
156
Max. 128 ZONEs and/or ZONE-ADDRESSes can be programmed but
only the zone numbers 01-32 can be used.
157
Max. number of alarm points per c.i.e. (microprocessor) is 512 and max.
number of alarm points per zone is 32, i.e. if more than 12 conventional zone
line inputs are used, care must be taken in order not to exceed 512 detectors
and/or manual call points connected to the c.i.e. (12 x 32 = 384; 128 + 384 =
512).
142
EBL128 Planning Instructions V1.1.x
Max. no.
128
200
Approx.
1000
32
16
50
157
512
50
5
8
200