Cc-Link Function Setting; Station Number Setting; Baud Rate Setting - Toshiba TOSVERT VF-S15 series Function Manual

Tosvert vf-s15 series cc-link option unit
Hide thumbs Also See for TOSVERT VF-S15 series:
Table of Contents

Advertisement

5.3.

CC-Link function setting

5.3.1. Station number setting

Use parameter c120 to set station number of the inverter.
Set this parameter within the range of 1 to 64.
Title
c120
*Use different station numbers for different devices. (If different devices have the same station
number, the communication cannot be performed properly.)
・ Set consecutive numbers for the station numbers. (Do not skip a number in sequence
like "station number 1 - station number 2 - station number 4".)
・ The station number does not have to match with the physical connection sequence.
(There is no problem with having the physical connection sequence like "station
number 1 - station number 3 - station number 4 - station number 2".)
・ One inverter occupies one station. (One remote device station)
・ "L.ERR" LED flickers if the setting is changed. When power is switched on again,
reset by parameter ( f899 = 1) or the RES signal is turned on, the setting value is
reflected and the LED turns off.

5.3.2. Baud rate setting

Set the transmission speed. (Refer to the manual for the CC-Link master module for
details of transmission speed.)
Title
c121
・ "L.ERR" LED flickers if the setting is changed. When power is switched on again,
reset by parameter ( f899 = 1) or the RES signal is turned on, the setting value is
reflected and the LED turns off.
Function
CC-Link station
number selection
Function
CC-Link baud rate selection
- 14 -
Description
1 to 64
Description
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
E658130