Mitsubishi Electric MN converter Operating Manual page 139

Electric air-conditioner network system
Hide thumbs Also See for MN converter:
Table of Contents

Advertisement

Operation Monitor Trouble
Trouble
The monitor display screen on the
operation monitor has red characters.
All of the characters on the monitor
display for some units are red.
The message of " G-50A can't Connect to
SMTP Server !
or G-50A Date Setting is wrong !!
Continue ?" is displayed at remote monitor
setting.
A message of " Monitor data size is very
large!! Please, delete old monitor data!!" is
displayed during collecting data.
Data becomes a red display and the "-"
display.
Malfunction Log Trouble
Trouble
Cannot clear malfunction log
There is an error code, but the contents of
the error are not displayed
Cause
Because of the increased re-transmission
process work due to abundant
communication noise, data may not be
monitored fully within the rated cycle.
There is no answer from the unit.(Cannot
communicate with the unit.)
The dial-up router is not connected. Or
connected but incorrectly.
The default gateway of G-50A is not set.
The incorrect display of the receiver
address is pointed out by SMTP.
The Monitor Finish Date is older than the
current date/time of G-50A.
The memory capacity to store data is
insufficient.
Since data cannot receive normally.
- There is too much number of a monitor.
- Data transforms itself by a noise.
Cause
The unit is not compatible with malfunction
log clear.
This is a newly added error code and is
not compatible with the Maintenance
Tools.
138
Repair
Please take a countermeasure against the
communication noise source in this case.
Error with unit.
Refer to the service handbook for that
unit.
By referring to Instruction Manual of
Dial-up router, connect or set correctly.
Set correctly by using the G-50A initial
setting tool. (Refer to Instruction Manual
of G-50A initial setting tool.)
Set the correct mailing address.
Set the monitor finish date correctly.
(However when connecting to G-50A in a
region with a time differential, set it by
considering the time in that place.)
Move to Offline Screen, and delete
unnecessary data.
- Reduce the number of a monitor.
- Cope with noise generating origin.
* Also when returning from a graph screen
to an operation screen, it may become a
red display and the "-" display, but it is
normal.
Repair
The malfunction log cannot be cleared.
Refer to the service handbook for that
unit.