Commercial Power Source Switching - Hitachi L300P Series Instruction Manual

Three-phase input 200v class; three-phase input 400v class;
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

4–22
Using Intelligent Input Terminals
Commercial
Power Source
Switching
Power source, 3-phase
MCCB
L1
L2
L3
The commercial power source switching function is useful in systems with excessive starting
torque requirements. This feature permits the motor to be started "across the line," sometimes
called a bypass configuration. After the motor is running, the inverter takes over to control the
speed. This feature can eliminate the need to oversize the inverter, reducing cost. However,
additional hardware such as magnetic contactors will be required to realize this function. For
example, a system may require 55KW to start, but only 15KW to run at constant speed. There-
fore, a 15KW rated inverter would be sufficient when using the commercial power source
switching.
The following block diagram shows an inverter system with bypass capability. When starting
the motor directly across the line, relay contacts Mg2 are closed, and Mg1 and Mg3 are open.
This is the bypass configuration, since the inverter is isolated from the power source and motor.
Then Mg1 contacts close about 0.5 to 1 second after that, supplying power to the inverter.
Mg2
GFI
Mg1
Switching to inverter control occurs after the motor is running at full speed. First, Mg2 relay
contacts open. Then about 0.5 to 1 seconds later, relay Mg3 contacts close, connecting the
inverter to the motor. The following timing diagram shows the event sequence:
Mg1
Mg2
Mg3
FW
Set to 0.5 to 1 sec typical
[CS]
B003 (Retry wait time
Inverter
before motor restart)
output
R
U
L300P
S
V
T
W
R0
T0
AL1
FW
[RV]
AL0
[CS]
AL2
CM1
H
O
L
Mg2/Mg3 delay time 0.5 to 1 sec.
Frequency matching
Normal operation
Thermal
switch
Mg3
Motor
t

Advertisement

Table of Contents
loading

Table of Contents