Facility Dc Power Connection; Power Phases And 3U Power Supply Enclosures - HP 279720-B21 - ProLiant BL p-Class F-GbE Interconnect Overview

Bladesystem p-class system overview and planning
Hide thumbs Also See for 279720-B21 - ProLiant BL p-Class F-GbE Interconnect:
Table of Contents

Advertisement

Figure 32: Maximum output power capacity
For more information about the HP BladeSystem p-Class Sizing Utility, refer to
http://www.hp.com/go/bladesystem/sizingutility

Facility DC power connection

Facility DC power requires a Facility DC Power Connection Option Kit to distribute the current through
the mini or scalable bus bars to the server blade enclosures. The HP BladeSystem p-Class system
requires –48 VDC with no more than ±10% voltage variance. If using facility DC power, power
supplies and power enclosures are not needed for operation, because the DC Power Connection
Option Kit provides power through a direct connection to the bus bars.

Power phases and 3U power supply enclosures

The HP BladeSystem p-Class solution is designed for AC input power from either single-phase or
three-phase power sources. Three-phase power supports maximum density configurations and is
highly recommended.
Geography and number of AC phases dictate the appropriate model of 3U power enclosure for the
data center. Each model of 3U power enclosure uses a different connector, as detailed in the
following chart. Additionally, each 3U power enclosure requires two separate 30 A power feeds.
45