Control Module - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
No.
Indicator or Port
1
Status indicator
2
LCD
3
MUS05A (DB26)
4
GE
5
CAN
6
RS485_1
7
FE_1
8
FE_2
9
USB Host
10
SD
11
DIP switch

2.5.4 Control Module

The control module in a standard configuration contains two ECMs, one dry
contact card, and one monitoring interface card from left to right. The four cards
are hot-swappable. One subrack is reserved above the dry contact card. A
backfeed protection card or dry contact extended card can be inserted into this
subrack.
Issue 02 (2024-01-05)
Description
● Red: A critical alarm has been generated, and the buzzer sounds
continuously.
● Yellow: A minor alarm has been generated, and the buzzer
buzzes intermittently at 2 Hz.
● Green: The UPS is running properly or a warning has been
generated.
● Off: The UPS display is not powered on.
Man-machine interface
Connects to the MDU and monitoring interface card.
Network port. A shielded cable is required.
Reserved
Reserved
Reserved
Reserved
● Insert a USB flash drive to import and export configuration files,
export run logs, and upgrade software.
● iManager-M service access is supported after a 4G module is
installed on some models.
NOTE
The USB port is protected by a security mechanism. Users can export and
import data and upgrade software only after being authenticated.
Reserved
Implements specific functions by using the DIP switch and specific
buttons; and controls the CAN communication build-out resistor in
a parallel system. For details, contact technical support.