Huawei NetCol5000-A050 User Manual page 77

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Figure 4-22 Oil trap and inverted trap (unit: mm)
Table 4-10 Specifications of the oil trap and inverted trap
No.
1
2
3
4
Note: No dent or bulge is allowed on the surface after the trap is shaped.
Issue 13 (2023-08-20)
Name
Copper Pipe Outer
Diameter and
Thickness (mm)
Oil trap
22.2 x 1.2
Inverted
22.2 x 1.2
trap of
gas pipes
Inverted
19.0 x 1.0
trap of
liquid
pipes
Inverted
15.9 x 1.0
trap of
liquid
pipes
Copyright © Huawei Digital Power Technologies Co., Ltd.
Technical Requirements
Inner diameter at the expanded
end of the copper pipe: 22.4 mm;
outer diameter at the shrunk end:
19.5 mm
Inner diameters at the two
expanded ends of the copper pipe:
22.6 mm
Inner diameters at the two
expanded ends of the copper pipe:
19.0 mm
Inner diameters at the two
expanded ends of the copper pipe:
16.3 mm
4 Installation
66

Advertisement

Table of Contents
loading

Table of Contents