Huawei NetCol5000-A050 User Manual page 133

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A050:
Table of Contents

Advertisement

NetCol5000-A050 In-row Air Cooled Smart Cooling
Product
User Manual
Table 4-14 DIP switch settings on T/H sensors
Locati
on
Air
return
side
Cold
aisle
Hot
aisle
After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
----End
Issue 13 (2023-08-20)
Display Name
Return air 2
temp/humid
Cold aisle 1
temp/humid
Cold aisle 2
temp/humid
Cold aisle 3
temp/humid
Cold aisle 4
temp/humid
Cold aisle 5
temp/humid
Hot aisle 1
temp/humid
Hot aisle 2
temp/humid
Hot aisle 3
temp/humid
Hot aisle 4
temp/humid
Hot aisle 5
temp/humid
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Addr
DIP Switch Sequence No.
ess
1
2
1
ON
OFF
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
21
ON
OFF
22
OFF
ON
23
ON
ON
24
OFF
OFF
25
ON
OFF
4 Installation
3
4
5
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
122

Advertisement

Table of Contents
loading

Table of Contents