Toshiba GF630 Instruction Manual page 41

Electromagnetic flowmeter detector
Hide thumbs Also See for GF630:
Table of Contents

Advertisement

 
 
 
 
7.2.3 Flow rate indication is not stable
 
 
 
                
 
 
 
Is power supply voltage
 
within the specified range?
 
 
                        
 
 
Are cables securely connected?
 
 
 
                        
 
Is the flowmeter grounded
         
with 100Ωor less ground
 
resistance?
                         
 
 
 
 
Is the detector pipe filled
 
with fluid?
                         
 
 
 
 
Is the fluid carrying bubbles?
 
                         
 
 
 
 
Is there high-voltage or large
 
current cable or equipment
 
 
near the flowmeter?
 
 
 
 
 
 
Contact your nearest Toshiba
 
representative.
 
 
 
START
YES
YES
YES
YES
NO
NO
 
NO
Use a power supply within the
specified range.
Connect each cable securely to the
NO
terminal board.
Ground the flowmeter with a copper
braid or wire(5.5 mm² minimum) to a
NO
good earth ground
(100ohm or less ground resistance)
NO
Design piping so that the detector
pipe is filled with fluid all the time.
Design piping so that the fluid does
YES
not carry bubbles.
Install the flowmeter away from
YES
equipment producing electromagnetic
or electro- static interference.
Note 1: If the detector tube is not filled with
operating fluid, the flow is indefinite and
measurement is impossible. Be sure to fill
the detector tube with operating fluid
before starting measurement.
−  40  − 
6F8A0882 
.