1MRK511407-UUS Rev. N
ANSI05000462 V1 EN-US
Figure 9:
Phasor measurement unit RES670
Application manual
Transformer
Setting of current input
for transformer functions:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Example how to set CT_WyePoint parameters in the IED
© 2017 - 2023 Hitachi Energy. All rights reserved
Transformer and
Line protection
Setting of current input
for transformer functions:
Set parameter
CT_WyePoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Analog inputs
Line
Reverse
Forward
Definition of direction for
directional
line functions
Setting of current input
for line functions:
Set parameter
CT_WyePoint with
Line as
reference object.
Correct setting is
"FromObject"
en05000462_ansi.vsd
Section 4
45