Section 16
Monitoring
•
Disabled
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input channel. This can be set
between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic communication.
16.6
Disturbance report DRPRDRE
16.6.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
J
M
N
16.6.2
Identification
Function description
Disturbance report
Disturbance report
Disturbance report
Disturbance report
248
It is important to set the time interval for cyclic events in an optimized way to minimize the
load on the station bus.
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
Increased the total number of recordings to 200 and events to 5000. Total number of
recordings (MaxNoStoreRec setting) is no longer configurable. MemUsed output is now
based on number of recordings to total number of recordings. Old disturbance records won't
be deleted based on the memory consumption.
2.2.5
-
2.2.6
-
2.2.6
-
IEC 61850 identification
DRPRDRE
A1RADR - A4RADR
B1RBDR - B22RBDR
C1RADR - C3RADR
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
-
-
-
-
-
-
Phasor measurement unit RES670
1MRK511407-UUS Rev. N
M12811-29 v3
M12811-34 v1
IP14584-1 v2
GUID-85FF8EB6-0D47-4776-8E1A-2F8F978B5F00 v3
M16055-1 v10
Application manual