Section 4
Analog and binary signal transfer for line differential protection
Table 5:
Relevant settings
Setting
IdMin
EndSection1
EndSection2
SlopeSection2
SlopeSection3
IdMinHigh
tIdMinHigh
IdUnre
I2/I1Ratio
I5/I1Ratio
CCCOpMode
VTOnLineGrp1
VTOnLineGrp2
C0
C1
NoOfLineEnds
NoOfCTSetsGrp1
NoOfCTSetsGrp2
IBase
Table continues on next page
42
Value
Remark
0.20
20 % of IBase = 1000 A
Must be set above the maximum possible charging current (in this
example set to approximately 2 x of that value).
1.00
100 % of IBase = 1000 A
3.00
300 % of IBase = 1000 A
0.50
Slope = 50 %
1.00
Slope = 100 %
1.00
100 % of IBase = 1000 A
1000
Interval of initial decreased sensitivity in ms.
3.00
300 % of IBase = 1000 A
Maximum through fault current calculated based on:
IECEQUATION15178 V1 EN-US
IECEQUATION15179 V1 EN-US
0.10
Ratio = 10 %
The value can be set this low because the 2
ignored if an internal fault is detected.
0.10
Ratio = 10 %
The value can be set this low because the 5
if an internal fault is detected and no tap transformer exists in the
protected zone.
1
The exact method with currents and voltages is used. Line
capacitances must be specified.
0
VT is placed on the bus.
0
VT is placed on the bus.
7.751e-9 x 200
Total zero sequence capacitance of 220kV on a 200 km power line.
12.74e-9 x 200
Total positive sequence capacitance of 220kV on a 200 km power line.
2
Number of physical line ends in the protected zone (setting used by
charging current compensation).
1
Number of three-phase CT groups at first line end, the currents of which
are connected to input group 1 (setting used by charging current
compensation).
1
Number of three-phase CT groups at second line end, the currents of
which are connected to input group 2 (setting used by charging current
compensation).
1000
Nominal current of the protected power line.
© 2017 - 2023 Hitachi Energy. All rights reserved
220
I
2.45
Through
3 (4.84 58.64)
1.2
I
1.2 2.45
kA
Through
I
dUnre
I
1
kA
Base
Communication set-up, 670/650 series
1MRK505382-UEN Rev. K
kA
2.94
kA
nd
harmonic block is
th
harmonic block is ignored
Application Guide