1MRK505382-UEN Rev. K
Setting
IntervIdMinHig
Idunre
CrossBlock
I2/I1Ratio
I5/I1Ratio
NegSeqDiff
IminNegSeq
NegSeqROA
AddDelay
ImaxAddDelay
CurveType
DefDelay
IDMTtMin
TD
p
a
b
c
Communication set-up, 670/650 series
Application Guide
IED 1
30.000 s
5.50 · IBase
1
15%
25%
On
0.04 · IBase
60.0 deg
Off
1.00 · IBase
15
0.100 s
0.010 s
0.00
0.02
0.14
1.00
1.00
© 2017 - 2023 Hitachi Energy. All rights reserved
Analog and binary signal transfer for line differential protection
IED 2
Description
30.000 s
Time interval when
IdMinHig is active (note
5)
5.50 · IBase
Unrestrained operate
(differential) current
limit (note 6)
1
CrossBlock logic
scheme applied (note
7)
15%
Second to fundamental
harmonic ratio limit
25%
Fifth to fundamental
harmonic ratio limit
On
Internal/external fault
discriminator enabled
(default)
0.04 · IBase
Minimum value of the
negative-sequence
current
60.0 deg
Operate angle (ROA)
for Internal/external
fault discriminator
(default)
Off
Additional delay
disabled (default)
1.00 · IBase
Not applicable in this
case (default)
15
Not applicable in this
case (default)
0.100 s
Not applicable in this
case (default)
0.010 s
Not applicable in this
case (default)
0.00
Not applicable in this
case (default)
0.02
Not applicable in this
case (default)
0.14
Not applicable in this
case (default)
1.00
Not applicable in this
case (default)
1.00
Not applicable in this
case (default)
Section 4
35