ABB ACS560 Firmware Manual page 306

General purpose drives
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

306 Parameters
No.
Name/Value
PID output
40.57
PID set1/set2
selection
PID set 1
PID set 2
DI1
DI2
DI3
DI4
DI5
DI6
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.58
Set 1 increase
prevention
No
Limiting
Ext PID min lim
Ext PID max lim
Other [bit]
40.59
Set 1 decrease
prevention
No
Limiting
Ext PID min lim
Description
PID controller output.
Selects the source that determines whether process PID
parameter set 1 (parameters 40.07...40.50) or set 2 (group
41 Process PID set
2) is used.
0. Process PID parameter set 1 in use.
1. Process PID parameter set 2 in use.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Prevention of PID integration term increase for PID set 1.
Increase prevention not in use.
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
The process PID integration term is not increased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
The process PID integration term is not increased when the
output of the external PID has reached its maximum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
Source selection (see
Terms and abbreviations
Prevention of PID integration term decrease for PID set 1.
Decrease prevention not in use.
The PID integration term is not decreased if the minimum
value for the PID output is reached. This parameter is valid
for the PID set 1.
The process PID integration term is not decreased when the
output of the external PID has reached its minimum limit. In
this setup, the external PID is used as a source for the
process PID. This parameter is valid for the PID set 1.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 273).
(see page 273).
(see page 273).
(see page 266).
(see page 266).
(see page 266).
on page 162). -
on page 162). -
Def/FbEq16
2
PID set 1
0
1
2
3
4
5
6
7
18
19
20
21
22
23
No
0
1
2
3
No
0
1
2