LG PQNFB17C0 Installation & Owner's Manual page 44

Table of Contents

Advertisement

34
INSTALLING ACP BACnet
Remote Shutdown function
ACP BACnet provides Remote Shutdown function.
After connecting the emergency sensor to ACP BACnet DI1, if the emergency sensor detects
emergency, it stops the operations of all connected equipments except the Chiller.
Caution
Remote Shutdown interface
To use the Remote Shutdown function, emergency sensor needs to be connected to ACP
y
BACnet DI1.
Please refer to each emergency sensor product manual for detail usage of emergency
y
sensors.
Setting Celsius/Fahrenheit
ACP BACnet provides Celsius/Fahrenheit setting function.
To send the Celsius temperature to the BMS, set [Fahrenheit] to 0.To send the Fahrenheit
temperature to the BMS, set [Fahrenheit] to 1.Proceed in the following order.
1.
When you press [SET] button, menu screen will be displayed. Use up and down (▲, ▼) buttons
of the ACP BACnet to select [Contents], and press [SET] button again. While [Fahrenheit] is
selected, pressing [SET] button will display the screen to select Celsius or Fahrenheit.
PQNFB17C0
Network Info
>
Contents
Function
Register FD
Click
[SET]
button
[ Contents 1/2 ]
Peak/Demand
ACP ID
Fahrenheit
>
Click
[SET]
button
NOT(0) / USE(1) : 0
0
0
0
[ Set Fah. ]