Code
Message
4699
BATTERY TEST IMPOSSIBLE
4763
REMOTE CONTROL ON
4764
REMOTE CONTROL OFF
Modifications reserved
OPM_SGS_USM_M75_M75_2US_V010.doc
Automatic Battery Test is not possible due to:
− No Utility Rectifier or Bypass.
− Battery not fully charged.
− Load is below 10% or above 80%.
Test is postponed for 1 week.
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only Local Panel.
1 = Only Remote Control.
2 = Both.
Inverter cannot be started or shutdown by remote control.
Commands source can be chosen depending on the value
of parameter (Service only):
0 = Only Local Panel.
1 = Only Remote Control.
2 = Both.
Meaning